ISA-101 vs ISA-18.2 vs ISA-5.1: which standard answers which question

Standards comparison · Reference · ~7 min

The three standards answer three different questions. ISA-101 covers the operator interface (HMI): how screens are structured, what colour means, how the HMI is built and maintained. ISA-18.2 covers the alarm system: what counts as an alarm, how alarms are prioritised and how the system is managed over its life. ISA-5.1 covers instrumentation: how an instrument is tagged and drawn on a P&ID. They meet at the edges, and a project that follows one usually touches the other two, but each has a job the others do not do.

In short

The short answer

Start from the question you are trying to answer:

If your question is…Look atWhat you get
How should the screens be organised, what does each colour mean, how big is the text?ISA-101A design approach and an HMI lifecycle, normally recorded in a project style guide
What counts as an alarm, what priority does it get, how do we stop alarm floods?ISA-18.2An alarm management lifecycle, from the plant's philosophy to audit
What do we call this transmitter and how is it drawn on the P&ID?ISA-5.1Tag format, letter codes and the bubble that shows where the instrument lives
What does a pump, tank or conveyor look like on the drawing?None of the threeOther drawing standards (see P&ID symbols) and the project's legend sheet

The sections below take each standard in turn: what it covers and, just as useful, what it leaves to someone else. This is a practitioner's summary, not a substitute for the standards themselves; the project specification and the documents it cites are what count when a requirement is in question.

ISA-101: the operator interface

ISA-101 is the standard for human-machine interfaces in process automation. It treats the HMI as something with a lifecycle (a style guide written first, then design, implementation, operation and maintenance under change control) and it deals with the questions an HMI designer actually meets: how displays are organised into a hierarchy, what colour is allowed to mean, how text is sized, and how the interface supports the operator's awareness of what the plant is doing. It is deliberately independent of the platform.

What it covers

What it does not

The full walk-through is in the ISA-101 guide.

ISA-18.2: the alarm system

ISA-18.2 is about managing alarm systems in the process industries; it is also published internationally as IEC 62682. Its starting point is a definition: an alarm indicates an equipment malfunction, a process deviation or an abnormal condition that requires a response. If nothing needs doing, it is not an alarm. Around that idea it frames alarm management as a lifecycle: the plant's alarm philosophy, identification of candidate alarms, rationalisation (cause, consequence, operator action, time to respond, priority), detailed design, implementation, operation and maintenance, monitoring and assessment, and change management and audit. The per-operator alarm-rate benchmarks people quote usually come from EEMUA 191, a separate and older guide.

What it covers

What it does not

The practical side, from rationalisation to showing priority on screen, is in alarm management.

ISA-5.1: instrument identification and symbols

ISA-5.1, “Instrumentation Symbols and Identification”, is the drawing-side standard. It defines the tag (function letters plus a loop number, such as FCV-104 or LSHH-401), the letter codes for the measured variable and the function, the bubble that shows where an instrument lives (field, DCS, PLC or shared display), and the line types between instruments. It is P&ID-centric: it exists so that everyone who reads a drawing arrives at the same picture of the loop.

What it covers

What it does not

Details and the letter table are in the ISA-5.1 reference and the instrument symbols guide.

What none of them covers

Some gaps catch teams out because they assume “the standard” settles them:

How they fit together in one project

The dependency runs in one direction: the screen shows tags and priorities that the other two standards produce.

The three standards in one project Three boxes from top to bottom. ISA-5.1 answers what the instrument is called and gives the tags on the P&ID. An arrow labelled tags leads to ISA-18.2, which answers when something is an alarm and gives the alarm priorities. An arrow labelled priorities leads to ISA-101, which answers how the operator sees and acts on it and gives the HMI style guide and the screens. ISA-5.1 · Instruments What is it called, and how is it drawn? → Tags on the P&ID tags ISA-18.2 · Alarms When is it an alarm, and how urgent is it? → Alarm philosophy, priorities priorities ISA-101 · The HMI How does the operator see it and act on it? → Style guide and screens
  1. ISA-5.1 first. The P&ID gives every instrument its tag and its mounting. These tags are the names everything else uses.
  2. ISA-18.2 next. Alarms are rationalised against those tags: cause, consequence, operator action, time to respond and priority.
  3. ISA-101 throughout. The HMI style guide fixes palette, sizes, symbols and hierarchy, and decides how tags and priorities appear: the tag exactly as on the P&ID, the priority as a colour plus a second cue.

In real projects the three overlap in time. The style guide is being written while the P&ID is still changing, and the alarm list is rationalised while screens are drawn. What matters is that none of the three is left to chance: when a tag changes, the screen follows; when a priority changes, the badge follows.

Apply them on the screen

The Symbol Builder starts from the calm palette and exports one image per state, with alarm priority badges and instrument bubbles in the ISA-5.1 outline. The builder is free to use, no account needed to draw; downloads need a free account, 5 a month on Free.

Open the builder → Read the ISA-101 guide →

Frequently asked questions

What is the difference between ISA-101 and ISA-18.2?

ISA-101 is about the operator interface: how screens are organised, what colour means, how the HMI is built and maintained. ISA-18.2 is about the alarm system behind it: what counts as an alarm, how it is prioritised and how the system is managed over time. ISA-101 leaves alarm management to ISA-18.2, and the HMI then shows the priorities that the ISA-18.2 process produces.

What is the difference between ISA-101 and ISA-5.1?

ISA-5.1 is a drawing standard: tags, letter codes and bubbles that identify instruments on a P&ID. ISA-101 is a design standard for the operator screen. A good HMI uses ISA-101 for layout and colour and carries the ISA-5.1 tags over exactly as the P&ID shows them, so operators can cross-reference screen and drawing.

Do I have to follow all three standards on a project?

ISA standards are voluntary on their own. They apply to a project when a contract, a company specification or a regulator requires them, so the project specification is where to look. Where nothing requires them they are still a useful common language: ISA-5.1 for the drawings, ISA-18.2 for the alarm list, ISA-101 for the screens.

Where do alarm colours come from, ISA-101 or ISA-18.2?

Both play a part. The alarm priorities and what each one means come from the alarm philosophy and the rationalisation that ISA-18.2 describes. How a priority looks on the screen, with its colour and a second cue that does not rely on colour, is an HMI decision made in the style guide, which is ISA-101 territory. The two have to agree.

Which standard should I read first if I design HMIs?

Start with ISA-101, because it covers the screens you build. Then learn enough of ISA-18.2 to ask the right questions about alarm priorities, and enough of ISA-5.1 to read the tags on the P&ID. The guides linked below follow that order.